# Gas Technician 2 (G.2) Practice Exam

Practise for the Ontario G2 exam with 30 free questions from Ontario Certification Registry, a score and explanations. The full 150-question PDF includes these 30 plus 120 more, with an answer key and references.

Try 30 questions freeFull 150-question PDF · $67.49 CAD

- Secure checkout by Stripe
- PDF emailed in minutes
- Yours to keep

Updated 2026-11-11.

![Gas Technician 2 (G.2) Practice Exam cover](https://tradecredentialregistry.com/exam-covers/g2-gas-technician-768.png)

Free practice test

## Try 30 questions free

Work through 30 questions, then see your score, results by topic and an explanation for every answer. No account or email needed.

These are 30 of the 150 questions in the full PDF. You can also read the questions and answers below.

## The full 150-question PDF

Includes the 30 free questions plus 120 additional questions, explanations and references. One payment, no subscription.

| Questions | 150, all original |
| --- | --- |
| Answer key | Correct answer, the reasoning, and a cited source for each question |
| Distinct references | 54 distinct citations across the bank |
| Free samples here | 30, with answers, below |
| Format | PDF, emailed on purchase, plus a download link valid 30 days |
| Price | $67.49 CAD, one payment, no subscription |

Payment is handled by Stripe. This is study material, not an official exam, and it is not affiliated with Skilled Trades Ontario, TSSA or the Red Seal program.

## Look inside the PDF

A preview of the question and answer-key layout, using questions from the free sample. The full guide contains all 150 questions.

![Preview of the printable question page, using free sample questions](https://tradecredentialregistry.com/exam-previews/g2-gas-technician-questions.png)![Preview of the answer key with explanations and source references](https://tradecredentialregistry.com/exam-previews/g2-gas-technician-answers.png)

## What this guide covers

Editorial study plan: 10 questions for each of TSSA curriculum modules 10 through 24. This is not a published TSSA exam weighting. The table shows the actual counts and shares in this guide.

| Major work activity | Questions here | Share of this guide |
| --- | --- | --- |
| A. Module 10: Advanced piping and tubing | 10 | 6.7% |
| B. Module 11: Basic electricity | 10 | 6.7% |
| C. Module 12: Mechanical and electronic controls | 10 | 6.7% |
| D. Module 13: Building as a system | 10 | 6.7% |
| E. Module 14: Domestic and non-vented appliances | 10 | 6.7% |
| F. Module 15: Gas meters, regulators and relief valves | 10 | 6.7% |
| G. Module 16: Domestic gas-fired refrigerators | 10 | 6.7% |
| H. Module 17: Conversion burners | 10 | 6.7% |
| I. Module 18: Water heaters and combination systems | 10 | 6.7% |
| J. Module 19: Forced warm-air heating | 10 | 6.7% |
| K. Module 20: Hydronic heating | 10 | 6.7% |
| L. Module 21: Space heating and decorative appliances | 10 | 6.7% |
| M. Module 22: Venting practices | 10 | 6.7% |
| N. Module 23: Forced-air add-on devices | 10 | 6.7% |
| O. Module 24: Air handling | 10 | 6.7% |

Coverage source: [TSSA training curriculum and certification policy](https://www.tssa.org/sites/default/files/2023-12/Gas--Oil-Policy---Sept%202023---Final-for-Publication.pdf)

## The mix of question types

This is our editorial study mix, not an official examination distribution.

| Type | Questions here | Share |
| --- | --- | --- |
| Knowledge and recall | 30 | 20% |
| Procedural and application | 90 | 60% |
| Critical thinking | 30 | 20% |

## 30 free sample questions from the Gas Technician 2 (G.2) bank

This fixed selection comes straight from the bank and covers every major work activity, with the answers and sources shown. Read them before you decide whether the rest is worth $67.49 to you.

### Question 1: One section of natural gas piping feeds both a 199,900 Btu/h water heater and an 80,000 Btu/h furnace. At 1,000 Btu/ft³, what flow must that section be sized to carry?

### Sample 1 · Activity A

**One section of natural gas piping feeds both a 199,900 Btu/h water heater and an 80,000 Btu/h furnace. At 1,000 Btu/ft³, what flow must that section be sized to carry?**

1. 200 ft³/h
2. 280 ft³/h (correct)
3. 80 ft³/h
4. 120 ft³/h

A section shared by both appliances must carry their combined load when both fire: (199,900 + 80,000) / 1,000 = 279.9, about 280 ft³/h. Sizing it for the larger appliance alone (200 ft³/h) starves both when they run together, and 120 ft³/h is only the difference between the loads. The 1,000 Btu/ft³ figure is the cited manual's simplified value; use the supplier's heating value and the required code tables for a real installation.

Navien NPE-2 Installation Manual, section 3.3, Connecting the Gas Supply. https://www.navieninc.com/downloads/npe-a-s-manuals-installation-manual-en/download.PDF

### Question 2: A sizing table (0.5 in. w.c. drop) lists 3/4 in. pipe at 199 ft³/h for 30 ft and 170 ft³/h for 40 ft, and 1 in. pipe at 374 and 320 ft³/h. A 180,000 Btu/h heater (1,000 Btu/ft³) is 25 ft of pipe away, and its fittings add 12 ft. What is the smallest size that works?

### Sample 2 · Activity A

**A sizing table (0.5 in. w.c. drop) lists 3/4 in. pipe at 199 ft³/h for 30 ft and 170 ft³/h for 40 ft, and 1 in. pipe at 374 and 320 ft³/h. A 180,000 Btu/h heater (1,000 Btu/ft³) is 25 ft of pipe away, and its fittings add 12 ft. What is the smallest size that works?**

1. 3/4 in.
2. 1 in. (correct)
3. 1/2 in.
4. 1 1/4 in.

Equivalent length is 25 + 12 = 37 ft, which is not a table column, so use the next longer column (40 ft). The load is 180,000 / 1,000 = 180 ft³/h, more than the 170 ft³/h that 3/4 in. carries at 40 ft, while 1 in. carries 320. Using the 25 ft pipe length alone (30 ft column, 199 ft³/h) is the mistake that wrongly passes 3/4 in. The values are from the cited manual's reference table; size real Ontario work with the code tables TSSA requires.

Navien NPE-2 Installation Manual, section 3.3, Connecting the Gas Supply. https://www.navieninc.com/downloads/npe-a-s-manuals-installation-manual-en/download.PDF

### Question 3: An S9200U1000, which supplies 120 V to its hot surface igniter, replaces a control that ran an 80 V igniter. Treating the igniter's resistance as fixed, how much power would the old igniter take?

### Sample 3 · Activity B

**An S9200U1000, which supplies 120 V to its hot surface igniter, replaces a control that ran an 80 V igniter. Treating the igniter's resistance as fixed, how much power would the old igniter take?**

1. 1.5 times its rating
2. 0.67 times its rating
3. The same as its rating
4. 2.25 times its rating (correct)

For a fixed resistance, P = V²/R, so power rises with the square of voltage: (120 / 80)² = 1.5² = 2.25. Answering 1.5 applies the voltage ratio as if current stayed constant, and 0.67 inverts the ratio. The element would run far above its design power, which is why the cross-reference table directs fitting a 120 V igniter where the old control ran an 80 V one; a real igniter's resistance changes with temperature, so 2.25 is an estimate.

Resideo S9200U1000 Instructions 69-2075EF-09, Installation and replacement requirements, pages 4 to 9. https://customer.resideo.com/resources/Techlit/TechLitDocuments/69-0000s/69-2075EF.pdf

### Question 4: A 24 V gas valve drawing 0.8 A is 40 m from its transformer, wired with two 18 AWG conductors of 21 Ω per km each. The transformer holds 24.0 V under load and the valve needs at least 20.4 V. What reaches the valve?

### Sample 4 · Activity B

**A 24 V gas valve drawing 0.8 A is 40 m from its transformer, wired with two 18 AWG conductors of 21 Ω per km each. The transformer holds 24.0 V under load and the valve needs at least 20.4 V. What reaches the valve?**

1. 23.3 V; it will operate
2. 22.7 V; it will operate (correct)
3. 10.6 V; it will not operate
4. 21.9 V; it will operate

Current goes out and back, so the loop is 80 m: 0.080 km × 21 Ω/km = 1.68 Ω, and the drop is 0.8 A × 1.68 Ω = 1.34 V, leaving 24.0 − 1.34 = 22.7 V, above the 20.4 V needed. Counting only one 40 m conductor gives 23.3 V, and dividing the resistance by the current instead of multiplying gives 21.9 V. Reading 21 Ω per 100 m instead of per km gives 10.6 V.

TSSA Gas Technician/Oil Burner Technician Policies and Procedures, updated March 2025, sections 19 and 21, G.2 curriculum scope; arithmetic uses the formula and assumptions stated in this question. https://www.tssa.org/sites/default/files/2023-12/Gas--Oil-Policy---Sept%202023---Final-for-Publication.pdf

### Question 5: With a VR8200 knob at PILOT and the red reset button held down, the pilot will not light. The supply valve is open and the pilot line is purged. Which cause fits?

### Sample 5 · Activity C

**With a VR8200 knob at PILOT and the red reset button held down, the pilot will not light. The supply valve is open and the pilot line is purged. Which cause fits?**

1. Power unit magnet too weak
2. No 24 V across TH and TR
3. Thermocouple output too low
4. Pilot orifice or tubing blocked (correct)

Holding the reset button passes pilot gas whether or not the thermocouple produces current, and 24 V operates only the main valve operators, so neither can stop the pilot lighting. That leaves the pilot gas path, and the service procedure lists a closed pilot adjustment screw, clogged pilot tubing or orifice, or a leak at the compression fitting. Thermocouple output and the power unit matter only once the button is released.

Resideo V8200/VR8200 Instructions 69-0422-05, Service, page 7. https://customer.resideo.com/resources/Techlit/TechLitDocuments/69-0000s/69-0422.pdf Also: Resideo V8200/VR8200 Instructions 69-0422-05, Startup and Checkout, Gas Control Knob Settings, page 5. https://customer.resideo.com/resources/Techlit/TechLitDocuments/69-0000s/69-0422.pdf

### Question 6: A VR8200 pilot goes out when the reset is released. The reset was held 1 minute, the flame covers 12 mm of the thermocouple tip, the connection is clean and tight, and open-circuit output is within the published range. Following Resideo's service steps, what comes next?

### Sample 6 · Activity C

**A VR8200 pilot goes out when the reset is released. The reset was held 1 minute, the flame covers 12 mm of the thermocouple tip, the connection is clean and tight, and open-circuit output is within the published range. Following Resideo's service steps, what comes next?**

1. Replace the thermocouple
2. Replace the gas control (correct)
3. Enlarge the pilot flame
4. Retighten the connection

Every earlier step of Resideo's procedure has passed: reset held long enough, pilot covering the 10 to 13 mm of tip the instructions call for, a clean secure connection, and open-circuit output within range, so the procedure ends with replacing the gas control, which cannot be repaired. The thermocouple is replaced only when its output is outside the range. In the field a loaded (closed-circuit) reading or a known-good thermocouple is a sensible cross-check before condemning the control.

Resideo V8200/VR8200 Instructions 69-0422-05, Service, page 7. https://customer.resideo.com/resources/Techlit/TechLitDocuments/69-0000s/69-0422.pdf

### Question 7: An NPE-240 (199,900 Btu/h) is set up to use room combustion air, supplied through an opening direct to outdoors. The manual requires 1 in² of free area per 4,000 Btu/h. What free area is needed?

### Sample 7 · Activity D

**An NPE-240 (199,900 Btu/h) is set up to use room combustion air, supplied through an opening direct to outdoors. The manual requires 1 in² of free area per 4,000 Btu/h. What free area is needed?**

1. 50 in² (correct)
2. 25 in²
3. 100 in²
4. 200 in²

199,900 / 4,000 = 49.98, so about 50 in² of free area, which matches the manual's table for this model. 200 in² is the indoor make-up air figure at 1 in² per 1,000 Btu/h, and 100 in² uses a 2,000 Btu/h ratio the question does not give. Free area is the open area left after louvres and screens, and in Ontario the more stringent of the manual and the adopted code applies.

Navien NPE-2 Installation Manual, sections 3.1 and 3.6, Location and Combustion Air. https://www.navieninc.com/downloads/npe-a-s-manuals-installation-manual-en/download.PDF Also: TSSA CAD Amendment FS-279-26, item 1.5, clause 4.1.5, effective 1 June 2026. https://www.tssa.org/sites/default/files/2026-04/Gaseous-Fuels-CAD-Amendment-Fuels-CAD-FS-279-26.pdf

### Question 8: A room-air (single-pipe) NPE-2's heat exchanger freezes overnight while the heater is idle. A dryer and bath fans ran for hours, the vent is intact and there are no water leaks. What is the likely cause?

### Sample 8 · Activity D

**A room-air (single-pipe) NPE-2's heat exchanger freezes overnight while the heater is idle. A dryer and bath fans ran for hours, the vent is intact and there are no water leaks. What is the likely cause?**

1. Condensate trap left dry
2. Low inlet gas pressure
3. Wrong gas-type DIP setting
4. Exhaust-driven backdraft (correct)

With room-air venting, negative house pressure can draw cold outdoor air backward through the vent and heat exchanger, and the manual warns this can freeze the heat exchanger. Hours of exhaust-fan and dryer operation while the heater sat idle fit that pattern, whereas gas-type, gas-pressure and condensate faults appear as combustion or error-code problems when it fires. The manual's remedy where backdrafting is possible is direct venting, along with correcting the depressurization.

Navien NPE-2 Installation Manual, sections 3.1 and 3.6, Location and Combustion Air. https://www.navieninc.com/downloads/npe-a-s-manuals-installation-manual-en/download.PDF

### Question 9: A new UGP-R30 range replaces an old one, and the old certified flexible connector looks undamaged. What does the manual require?

### Sample 9 · Activity E

**A new UGP-R30 range replaces an old one, and the old certified flexible connector looks undamaged. What does the manual require?**

1. Reuse it after a leak test
2. Fit a new certified connector (correct)
3. Reuse it with new fittings
4. Reuse it if under 3 ft long

The manual says never to reuse an old connector when installing a new range; connectors and their fittings are made for the original installation only and are not intended for repeated bending. A passing leak test shows the joint is tight today, not that a flexed, aged connector is sound. Fit a new certified connector, use gas-resistant compound on male threads, and leak test every joint.

Unique UGP-R30 OTH LP Installation and User Manual, Installation, Anti-Tip and Gas Conversion, pages 11 to 24. https://cdn.shopify.com/s/files/1/0744/6947/4587/files/UGP_R30_OTH_LP_Install_User_Manual_v6Final_14d493dd-2758-4520-895c-88a28c8a86de.pdf

### Question 10: Right after cleaning, the front-left cooktop burner burns with flames on one side only. The other three burners are normal. What is the likely cause?

### Sample 10 · Activity E

**Right after cleaning, the front-left cooktop burner burns with flames on one side only. The other three burners are normal. What is the likely cause?**

1. Manifold pressure too low
2. Cap or spreader misaligned (correct)
3. Wrong orifice for the gas
4. Weak spark battery

A fault that appears on one burner straight after it was cleaned and reassembled points to that burner: the troubleshooting table lists uneven burner alignment (caps not seated evenly) and clogged ports for uneven flame. Low manifold pressure would affect every burner, the orifices were not touched, and the spark only lights the burner, it does not shape the flame. Reseat the spreader and cap, and check the ports are clear and dry.

Unique UGP-R30 OTH LP Installation and User Manual, Alignments, Cleaning and Maintenance, pages 28 to 34. https://cdn.shopify.com/s/files/1/0744/6947/4587/files/UGP_R30_OTH_LP_Install_User_Manual_v6Final_14d493dd-2758-4520-895c-88a28c8a86de.pdf

### Question 11: A natural gas V8200 is firing. With its regulator screw fully clockwise, the outlet reads 2.6 in. w.c. against a 3.5 in. w.c. nameplate. What does Resideo say to do next?

### Sample 11 · Activity F

**A natural gas V8200 is firing. With its regulator screw fully clockwise, the outlet reads 2.6 in. w.c. against a 3.5 in. w.c. nameplate. What does Resideo say to do next?**

1. Replace the gas control
2. Fit a larger main orifice
3. Check TH-TR coil voltage
4. Measure the inlet pressure (correct)

When the outlet setting cannot be reached by adjustment, Resideo directs a manometer reading at the inlet pressure tap; only if inlet is in the normal range (5.0 to 7.0 in. w.c. for natural gas) is the control replaced, otherwise the supply is corrected. Replacing the control first skips that check. The coil is already energized because the main burner is firing, and a larger orifice cannot raise the regulated outlet pressure.

Resideo V8200/VR8200 Instructions 69-0422-05, Check and Adjust Gas Input and Burner Ignition, pages 6 to 7. https://customer.resideo.com/resources/Techlit/TechLitDocuments/69-0000s/69-0422.pdf

### Question 12: Only a furnace rated 80,000 Btu/h input is running. Its meter's 2 cu ft test dial makes one turn in 72 s. Using a supplied 1,000 Btu/cu ft, what does this show?

### Sample 12 · Activity F

**Only a furnace rated 80,000 Btu/h input is running. Its meter's 2 cu ft test dial makes one turn in 72 s. Using a supplied 1,000 Btu/cu ft, what does this show?**

1. Overfired by 64,000 Btu/h
2. Overfired by 20,000 Btu/h (correct)
3. Underfired by 8,000 Btu/h
4. Underfired by 30,000 Btu/h

Flow is 2 cu ft x 3,600 / 72 s = 100 cu ft/h, and 100 x 1,000 = 100,000 Btu/h, which is 20,000 Btu/h (25%) above the nameplate. Forgetting the 2 cu ft dial size gives 50,000 (30,000 under), multiplying 2 x 72 gives 144,000, and reading 72 s as 72 cu ft/h gives 72,000. Confirm the heating value with the utility and bring the input to nameplate by checking manifold pressure and orifice under the appliance instructions.

TSSA Gas Technician/Oil Burner Technician Policies and Procedures, updated March 2025, sections 19 and 21, G.2 curriculum scope; arithmetic uses the formula and assumptions stated in this question. https://www.tssa.org/sites/default/files/2023-12/Gas--Oil-Policy---Sept%202023---Final-for-Publication.pdf

### Question 13: A UGP sits in a closed alcove with its minimum clearances and runs warm on hot, humid days. What does the manual recommend for the alcove?

### Sample 13 · Activity G

**A UGP sits in a closed alcove with its minimum clearances and runs warm on hot, humid days. What does the manual recommend for the alcove?**

1. A low vent and a high vent (correct)
2. Supply raised to 13 in. w.c.
3. A larger burner jet
4. One vent at floor level

For a confined alcove the manual recommends two vents, one about 6 in. (150 mm) off the floor and one at or above the appliance top, so hot air leaves and cooler air crosses the rear fins like air through a radiator. A single low vent gives the hot air no way out. More heat input cannot fix poor heat rejection, and supply pressure must stay within 11 to 12 in. w.c.

Unique UGP-6C/8C/10C Owner Manual, Installation and heat shield, printed pages 3 to 5. https://uniqueappliances.com/cdn/shop/files/Final-UGP6C-8C-10C-SM-CM-Manual-ENG-9RVSSO-C-2018-Singlesided.pdf

### Question 14: A level UGP has warmed up and defrosted. Its burner shows a small steady flame with the thermostat knob near MIN, and turning the knob to MAX gives a full flame at once. What explains the warm cabinet?

### Sample 14 · Activity G

**A level UGP has warmed up and defrosted. Its burner shows a small steady flame with the thermostat knob near MIN, and turning the knob to MAX gives a full flame at once. What explains the warm cabinet?**

1. Burner held at bypass rate (correct)
2. Partly blocked burner jet
3. Supply below 11 in. w.c.
4. Flame safety valve shut

At MIN the thermostat closes its main valve and the burner runs only at the bypass rate, and the manual warns that left there for long the fridge will defrost. The instant full flame at MAX rules out a blocked jet or low supply pressure, either of which would keep the flame small at any setting, and the burner is lit, so the flame safety has not closed. Set the knob closer to MAX in hot weather and allow 24 hours before readjusting.

Unique UGP-6C/8C/10C Owner Manual, General Operating Instructions and importance of levelling, printed pages 6 to 9. https://uniqueappliances.com/cdn/shop/files/Final-UGP6C-8C-10C-SM-CM-Manual-ENG-9RVSSO-C-2018-Singlesided.pdf

### Question 15: A boiler will be converted with a CG4 at 140 MBH. Its chamber is 11 in. wide and 10 in. high. Beckett lists minimum width x height of 9 x 9 in. at 105 MBH, 10.5 x 10.5 in. at 140 MBH and 11.5 x 11.5 in. at 175 MBH. What does this show?

### Sample 15 · Activity H

**A boiler will be converted with a CG4 at 140 MBH. Its chamber is 11 in. wide and 10 in. high. Beckett lists minimum width x height of 9 x 9 in. at 105 MBH, 10.5 x 10.5 in. at 140 MBH and 11.5 x 11.5 in. at 175 MBH. What does this show?**

1. Large enough for 175 MBH
2. Large enough for 140 MBH
3. Too small for 105 MBH
4. Too small for 140 MBH (correct)

Both dimensions must meet the minimum for the firing rate: the 11 in. width passes 140 MBH, but the 10 in. height is short of 10.5 in., so the chamber is too small at 140 MBH. Checking only the width is the tempting mistake. The chamber meets 9 x 9 in., so 105 MBH fits, while 175 MBH needs 11.5 x 11.5 in.; the firing rate must also suit the appliance's rated input.

Beckett CG4 Gas Burner product and application information, certified conversion-burner application. https://www.beckettcorp.com/product/cg4-gas-burner-80-to-250-mbh-ac-power/

### Question 16: An oil furnace's nameplate input is 0.85 USgph. Beckett converts gph to gas input at x 140,000 Btu/h and requires the gas rate within 5% above to 10% below that input. Which configuration rate is acceptable?

### Sample 16 · Activity H

**An oil furnace's nameplate input is 0.85 USgph. Beckett converts gph to gas input at x 140,000 Btu/h and requires the gas rate within 5% above to 10% below that input. Which configuration rate is acceptable?**

1. 140,000 Btu/h
2. 100,000 Btu/h
3. 110,000 Btu/h (correct)
4. 130,000 Btu/h

0.85 x 140,000 = 119,000 Btu/h, so the window is 119,000 x 0.90 = 107,100 to 119,000 x 1.05 = 124,950 Btu/h, and only 110,000 fits. 130,000 is 9% above, acceptable only if the 10% allowance is wrongly applied upward; 100,000 is 16% low and risks flue-gas condensation; 140,000 treats the nozzle as 1.0 gph. The installed rate is then confirmed with the correct orifice at 3.5 in. w.c. manifold.

TSSA Gas Technician/Oil Burner Technician Policies and Procedures, updated March 2025, sections 19 and 21, G.2 curriculum scope; arithmetic uses the formula and assumptions stated in this question. https://www.tssa.org/sites/default/files/2023-12/Gas--Oil-Policy---Sept%202023---Final-for-Publication.pdf Also: Beckett CG4 Burner Manual 6104 BCG4 R04, Verify Burner Selection, pages 9 to 11. https://www.beckettcorp.com/wp-content/uploads/2022/05/6104BCG4.pdf

### Question 17: A new NPE-2 in a newly plumbed house gives weak flow at every hot tap, while cold flow is normal and all isolation valves are fully open. What should be serviced first?

### Sample 17 · Activity I

**A new NPE-2 in a newly plumbed house gives weak flow at every hot tap, while cold flow is normal and all isolation valves are fully open. What should be serviced first?**

1. The heat exchanger (flush)
2. The cold inlet water filter (correct)
3. The DHW flow sensor
4. The pressure relief valve

Navien says to clean the inlet water filter inside the cold water inlet after installation, then test for proper flow and leaks, and to tell the owner it needs periodic cleaning; debris from new piping collects there. Flushing for scale is the tempting answer, but a brand-new heat exchanger has had no time to scale. A relief valve does not restrict delivery to the taps.

Navien NPE-2 Installation Manual, section 3.4, Connecting the Water Supply. https://www.navieninc.com/downloads/npe-a-s-manuals-installation-manual-en/download.PDF

### Question 18: A supplied rule gives output kW = 0.07 x flow in L/min x rise in °C. A heater's output is 50 kW (input 58 kW). Inlet water is 8 °C, the set point 48 °C, and two showers draw 9.5 L/min of hot water each. What is expected?

### Sample 18 · Activity I

**A supplied rule gives output kW = 0.07 x flow in L/min x rise in °C. A heater's output is 50 kW (input 58 kW). Inlet water is 8 °C, the set point 48 °C, and two showers draw 9.5 L/min of hot water each. What is expected?**

1. Keeps up; it needs 26.6 kW
2. Keeps up; within 58 kW input
3. Short; it needs 53.2 kW (correct)
4. Short; it needs 63.8 kW

The rise is 48 - 8 = 40 °C and the flow 2 x 9.5 = 19 L/min, so the load is 0.07 x 19 x 40 = 53.2 kW, more than the 50 kW output, and the outlet temperature will sag. 26.6 kW counts one shower, 63.8 kW uses 48 °C as the rise, and comparing with the 58 kW input ignores efficiency. At a 40 °C rise this heater can supply about 50 / 2.8 = 17.9 L/min.

TSSA Gas Technician/Oil Burner Technician Policies and Procedures, updated March 2025, sections 19 and 21, G.2 curriculum scope; arithmetic uses the formula and assumptions stated in this question. https://www.tssa.org/sites/default/files/2023-12/Gas--Oil-Policy---Sept%202023---Final-for-Publication.pdf

### Question 19: After the safe-start check on an S9200U1000 heat call (PS = pressure switch, HSI = hot surface igniter), which order is correct?

### Sample 19 · Activity J

**After the safe-start check on an S9200U1000 heat call (PS = pressure switch, HSI = hot surface igniter), which order is correct?**

1. Inducer, PS closes, HSI, prepurge, valve
2. Inducer, prepurge, PS closes, HSI, valve
3. Inducer, PS closes, prepurge, HSI, valve (correct)
4. PS closes, inducer, prepurge, HSI, valve

The control energizes the inducer, waits for the pressure switch to close, runs prepurge, energizes the HSI for its warm-up period, then energizes the gas valve for trial for ignition. Prepurge cannot start until the switch proves the inducer's draft, which rules out the tempting second order. A switch that closes before the inducer runs is a fault, and the igniter is not heated until prepurge ends.

Resideo S9200U1000 Instructions 69-2075EF-09, Normal Heat Mode and safety circuit responses, pages 13 to 15. https://customer.resideo.com/resources/Techlit/TechLitDocuments/69-0000s/69-2075EF.pdf

### Question 20: On an S9200U1000 heat call, the inducer never starts and the control flashes a fault code. With its wires removed and no draft applied, the pressure switch reads 0 ohms across its terminals, and its hose is dry and clear. What is indicated?

### Sample 20 · Activity J

**On an S9200U1000 heat call, the inducer never starts and the control flashes a fault code. With its wires removed and no draft applied, the pressure switch reads 0 ohms across its terminals, and its hose is dry and clear. What is indicated?**

1. Switch contacts stuck closed (correct)
2. Water trapped in the hose
3. Inducer relay welded on
4. Wiring shorted at switch

The control must find the pressure switch open before it starts the inducer; a closed switch holds the sequence and flashes an error. Reading 0 ohms with the wires off and no draft proves the contacts themselves are closed, which rules out the tempting shorted-wiring cause. A welded inducer relay would run the inducer, and the hose is clear and dry, so replace the switch with the specified part.

Resideo S9200U1000 Instructions 69-2075EF-09, Normal Heat Mode and safety circuit responses, pages 13 to 15. https://customer.resideo.com/resources/Techlit/TechLitDocuments/69-0000s/69-2075EF.pdf

### Question 21: A wet-rotor circulator on a loop running at 82 °C will be replaced. Power is locked out. What must be done before its flange bolts are loosened?

### Sample 21 · Activity K

**A wet-rotor circulator on a loop running at 82 °C will be replaced. Power is locked out. What must be done before its flange bolts are loosened?**

1. Close the supply-side valve
2. Close the cold-water fill valve
3. Close the expansion tank valve
4. Cool it, close valves both sides (correct)

Water at 82 °C under system pressure can scald when a flange opens, so let the loop cool, close the isolation valves on both sides of the pump, then relieve the small trapped volume into a pail. Closing one side leaves the pump open to the rest of the loop through the other. Closing the fill or expansion tank valve does not isolate the pump at all.

Red Seal Occupational Standard - Plumber, tasks F-17 and F-18, hydronic installation, testing and service. https://red-seal.ca/_conf/assets/custom/docms/plumber/rsos-eng.pdf

### Question 22: A zone flow meter reads 0.20 kg/s with 70 °C supply and 50 °C return. Using Q = 4.19 x flow (kg/s) x temperature drop (°C) in kW, how does it compare with a 20 kW design load?

### Sample 22 · Activity K

**A zone flow meter reads 0.20 kg/s with 70 °C supply and 50 °C return. Using Q = 4.19 x flow (kg/s) x temperature drop (°C) in kW, how does it compare with a 20 kW design load?**

1. 16.8 kW, short of the load (correct)
2. 41.9 kW, above the load
3. 58.7 kW, above the load
4. 4.0 kW, short of the load

The drop is 70 - 50 = 20 °C, so Q = 4.19 x 0.20 x 20 = 16.8 kW, about 3.2 kW short of the 20 kW load. Using the supply temperature alone gives 58.7 kW, the return alone 41.9 kW, and leaving out the 4.19 gives 4.0 kW. The formula assumes water; a glycol mix carries less heat per kilogram.

TSSA Gas Technician/Oil Burner Technician Policies and Procedures, updated March 2025, sections 19 and 21, G.2 curriculum scope; arithmetic uses the formula and assumptions stated in this question. https://www.tssa.org/sites/default/files/2023-12/Gas--Oil-Policy---Sept%202023---Final-for-Publication.pdf

### Question 23: The LT2 chart keeps combustible mantels behind a 45° line rising from the outermost corner of the trim. That corner is 760 mm above the floor, and the mantel's underside will be 1,000 mm above the floor. How far forward of the corner may its front edge reach?

### Sample 23 · Activity L

**The LT2 chart keeps combustible mantels behind a 45° line rising from the outermost corner of the trim. That corner is 760 mm above the floor, and the mantel's underside will be 1,000 mm above the floor. How far forward of the corner may its front edge reach?**

1. 120 mm
2. 240 mm (correct)
3. 480 mm
4. 170 mm

The underside is 1,000 - 760 = 240 mm above the corner, and a 45° line moves forward one unit for each unit of rise, so the mantel's lower front edge may reach 240 mm forward and no more. 170 mm comes from multiplying by sin 45°, and 120 mm or 480 mm halve or double the rise. Check the actual model's chart and its other listed clearances before framing.

Valor LT2 2700KN/KP Installation Manual 4009502-11, Specifications and Installation Planning, pages 6 to 20. https://www.valorfireplaces.com/media/LT2/English/2700KN-KP-Installation.pdf

### Question 24: An LT2 (natural gas) with the birch log set has black carbon on the logs and soot at the outside termination. Manifold pressure reads the rated 3.9 in w.c. on high, and the flame is tall, orange and lazy with smoke off the tips. What is the most likely cause?

### Sample 24 · Activity L

**An LT2 (natural gas) with the birch log set has black carbon on the logs and soot at the outside termination. Manifold pressure reads the rated 3.9 in w.c. on high, and the flame is tall, orange and lazy with smoke off the tips. What is the most likely cause?**

1. Wrong pilot injector fitted
2. Burner overfired on high
3. Supply pressure too low
4. Air shutter closed too far (correct)

The manual warns that too little aeration forms black carbon on logs and stains the termination, and a lazy orange flame trailing smoke is the classic sign of too little primary air; it notes this log set is prone to soot with the shutter at minimum. Manifold pressure at the rated value rules out overfiring, and low supply pressure would show up as low manifold pressure. Open the shutter in small steps, check log placement against the diagram, and judge the flame again after a 15-minute warm-up.

Valor LT2 2700KN/KP Installation Manual 4009502-11, Installation, Fuel Bed Instructions. https://www.valorfireplaces.com/media/LT2/English/2700KN-KP-Installation.pdf

### Question 25: A 2 in PVC exhaust is being joined to an NPE-2's vent collar. Which method follows the manual?

### Sample 25 · Activity M

**A 2 in PVC exhaust is being joined to an NPE-2's vent collar. Which method follows the manual?**

1. Full 70 mm insertion, no cement (correct)
2. Prime and cement it in the collar
3. Grease the end, insert 70 mm
4. Start with a street elbow there

Mark the pipe 2-3/4 in (70 mm) from a square, deburred end, push it in with a twist until the mark disappears, and tighten the clamp; no primer or cement is used on the appliance connection, and water, not grease, is the lubricant. The run must start with straight pipe because an elbow at the collar will not seal. The vent installation detector shows error 762 if the pipe is not fully seated.

Navien NPE-2 Installation Manual, section 3.6, Venting for Combustion Air. https://www.navieninc.com/downloads/npe-a-s-manuals-installation-manual-en/download.PDF

### Question 26: An NPE-2 2 in vent has 40 ft of straight pipe, three 90° elbows, two 45° elbows and a PVC concentric termination. The manual allows 75 ft, counting 8 ft per 90°, 4 ft per 45° and 5 ft for the termination. What is the result?

### Sample 26 · Activity M

**An NPE-2 2 in vent has 40 ft of straight pipe, three 90° elbows, two 45° elbows and a PVC concentric termination. The manual allows 75 ft, counting 8 ft per 90°, 4 ft per 45° and 5 ft for the termination. What is the result?**

1. 72 ft, within the limit
2. 85 ft, over the limit
3. 66 ft, within the limit
4. 77 ft, over the limit (correct)

40 + (3 x 8) + (2 x 4) + 5 = 77 ft, which is 2 ft over the 75 ft maximum, so the run must be shortened, simplified or changed to 3 in pipe. Leaving out the termination gives 72 ft, using the 3 in vent values of 5 ft and 3 ft gives 66 ft, and counting the 45s as 90s gives 85 ft. The run must also stay within the six 90° elbows allowed for 2 in vent.

Navien NPE-2 Installation Manual, section 3.6, Venting for Combustion Air. https://www.navieninc.com/downloads/npe-a-s-manuals-installation-manual-en/download.PDF

### Question 27: A bypass humidifier has a 24 Vac solenoid valve that should open only during heating cycles. How is it powered from the S9200U1000?

### Sample 27 · Activity N

**A bypass humidifier has a 24 Vac solenoid valve that should open only during heating cycles. How is it powered from the S9200U1000?**

1. Directly from HUM and neutral
2. Directly from EAC and neutral
3. 24 V transformer fed from HUM (correct)
4. 24 V transformer fed from EAC

HUM is a 120 Vac output that energizes with the inducer, so it follows heating cycles, but 120 V would burn out a 24 V coil; feed a 120/24 V transformer from HUM and a neutral and wire the solenoid and humidistat as the humidifier's diagram shows. The EAC output runs whenever the circulator runs, including cooling and fan-only, so it would humidify at the wrong times. Keep the transformer's primary current within the HUM output rating.

Resideo S9200U1000 Instructions 69-2075EF-09, Tables 5 and 6 and accessory wiring, pages 8 to 10. https://customer.resideo.com/resources/Techlit/TechLitDocuments/69-0000s/69-2075EF.pdf Also: Resideo S9200U1000 Instructions 69-2075EF-09, Humidity Control and Electronic Air Cleaner, page 15. https://customer.resideo.com/resources/Techlit/TechLitDocuments/69-0000s/69-2075EF.pdf

### Question 28: A furnace's 24 V, 40 VA transformer feeds the control (0.5 A), gas valve (0.6 A) and an A/C contactor (0.4 A). A 24 V humidifier solenoid (0.7 A) that opens only during heating is added. What is the largest simultaneous load?

### Sample 28 · Activity N

**A furnace's 24 V, 40 VA transformer feeds the control (0.5 A), gas valve (0.6 A) and an A/C contactor (0.4 A). A 24 V humidifier solenoid (0.7 A) that opens only during heating is added. What is the largest simultaneous load?**

1. 52.8 VA, over the rating
2. 43.2 VA, over the rating (correct)
3. 26.4 VA, within the rating
4. 36.0 VA, within the rating

In heating the control, valve and solenoid draw 0.5 + 0.6 + 0.7 = 1.8 A, and 1.8 x 24 = 43.2 VA, above the 40 VA rating; in cooling only 0.5 + 0.4 = 0.9 A (21.6 VA) flows. Adding every load gives 52.8 VA, but the contactor and solenoid are never on together, while 36.0 VA and 26.4 VA leave the solenoid out. Give the humidifier its own transformer rather than overload the furnace one.

TSSA Gas Technician/Oil Burner Technician Policies and Procedures, updated March 2025, sections 19 and 21, G.2 curriculum scope; arithmetic uses the formula and assumptions stated in this question. https://www.tssa.org/sites/default/files/2023-12/Gas--Oil-Policy---Sept%202023---Final-for-Publication.pdf

### Question 29: A furnace's rating plate allows a 45 to 75 °F temperature rise, and the manual says to aim for mid-range. What is that target rise in Celsius?

### Sample 29 · Activity O

**A furnace's rating plate allows a 45 to 75 °F temperature rise, and the manual says to aim for mid-range. What is that target rise in Celsius?**

1. A 33 °C rise (correct)
2. A 108 °C rise
3. A 60 °C rise
4. A 16 °C rise

Mid-range is (45 + 75) / 2 = 60 °F of rise, and a temperature difference converts by 5/9 only, so 60 x 5/9 = 33 °C; the manual's table lists the same range as 25 to 42 °C. Subtracting 32 first gives 16 °C, which treats a difference as a thermometer reading, and multiplying by 9/5 gives 108. One worked example in the NPF text prints 15 °C, the same slip, while its table is correct.

Navien NPF Installation and Operation Manual, sections 2.10, 7.2 and 7.3, Ducting, Temperature Rise and Airflow Data. https://www.navieninc.com/downloads/npf-installation-and-operation-manual-en/download.PDF

### Question 30: A furnace with 60,000 Btu/h input and 90% steady-state efficiency shows 70 °F return and 130 °F supply. Using Q = 1.08 x CFM x rise (°F), what airflow is it moving?

### Sample 30 · Activity O

**A furnace with 60,000 Btu/h input and 90% steady-state efficiency shows 70 °F return and 130 °F supply. Using Q = 1.08 x CFM x rise (°F), what airflow is it moving?**

1. 833 CFM (correct)
2. 385 CFM
3. 926 CFM
4. 900 CFM

Output is 60,000 x 0.90 = 54,000 Btu/h and the rise is 130 - 70 = 60 °F, so CFM = 54,000 / (1.08 x 60) = 833. Using the 60,000 input gives 926, dropping the 1.08 gives 900, and using the 130 °F supply temperature instead of the rise gives 385. The result is an estimate; confirm the rise against the rating plate range.

TSSA Gas Technician/Oil Burner Technician Policies and Procedures, updated March 2025, sections 19 and 21, G.2 curriculum scope; arithmetic uses the formula and assumptions stated in this question. https://www.tssa.org/sites/default/files/2023-12/Gas--Oil-Policy---Sept%202023---Final-for-Publication.pdf

## Before you buy

- These questions use the cited occupational standards, curriculum and technical references. Nothing here is reproduced from a real exam.
- Passing this does not guarantee passing the certifying exam, and nothing here is a substitute for the training standard or your in-school hours.
- It is a PDF. There is no login, no expiry and no subscription, and you can print it.
- Automated structure and distribution checks are complete. Technical accuracy review by a licensed tradesperson remains outstanding.

Questions about your purchase or a missing PDF? [Contact Blue Crane Works](mailto:info@bluecraneworks.ca) with the email used at checkout. The download link lasts 30 days; your saved PDF does not expire.

## Where the exam facts on this page come from

Editorial study plan: 10 questions for each of TSSA curriculum modules 10 through 24. This is not a published TSSA exam weighting. The regulation and issuing authority explain the actual credential and examination requirements.

- [TSSA training curriculum and certification policy](https://www.tssa.org/sites/default/files/2023-12/Gas--Oil-Policy---Sept%202023---Final-for-Publication.pdf)
- [O. Reg. 215/01, fuel industry certificates](https://www.ontario.ca/laws/regulation/010215)
- [TSSA fuel certification and examination information](https://www.tssa.org/fuels-industry-professional)

## The free reference material for this trade

Everything about the certification itself, the classification, the hours, the ratio and the official sources, stays free on this site and always will. The practice exam is the only thing here that costs anything.

- [Gas Technician 2 (G.2): the full certification record](https://tradecredentialregistry.com/canada/ontario/certificates/g2-gas-technician/)
- [Which Ontario trades are compulsory, and what that means for you](https://tradecredentialregistry.com/canada/ontario/compulsory-trades/)
- [Which Ontario safety tickets actually expire](https://tradecredentialregistry.com/canada/ontario/safety-training/)
- [Construction Electrician (309A) Practice Exam: 150 questions](https://tradecredentialregistry.com/practice-exams/309a-electrician-construction-and-maintenance/)
- [Plumber (306A) Practice Exam: 150 questions](https://tradecredentialregistry.com/practice-exams/306a-plumber/)
- [Industrial Mechanic Millwright (433A) Practice Exam: 150 questions](https://tradecredentialregistry.com/practice-exams/433a-industrial-mechanic-millwright/)
- [Automotive Service Technician (310S) Practice Exam: 150 questions](https://tradecredentialregistry.com/practice-exams/310s-automotive-service-technician/)
- [Ontario workplace fatalities and critical injuries by sector](https://tradecredentialregistry.com/canada/ontario/workplace-safety/)
- [Every practice exam we publish](https://tradecredentialregistry.com/practice-exams/)

## Other practice exams

- [![](https://tradecredentialregistry.com/exam-covers/309a-electrician-construction-and-maintenance-384.png)309A Construction Electrician](https://tradecredentialregistry.com/practice-exams/309a-electrician-construction-and-maintenance/)
- [![](https://tradecredentialregistry.com/exam-covers/306a-plumber-384.png)306A Plumber](https://tradecredentialregistry.com/practice-exams/306a-plumber/)
- [![](https://tradecredentialregistry.com/exam-covers/433a-industrial-mechanic-millwright-384.png)433A Industrial Mechanic Millwright](https://tradecredentialregistry.com/practice-exams/433a-industrial-mechanic-millwright/)
- [![](https://tradecredentialregistry.com/exam-covers/310s-automotive-service-technician-384.png)310S Automotive Service Technician](https://tradecredentialregistry.com/practice-exams/310s-automotive-service-technician/)
- [![](https://tradecredentialregistry.com/exam-covers/g3-gas-technician-384.png)G.3 Gas Technician 3](https://tradecredentialregistry.com/practice-exams/g3-gas-technician/)
- [![](https://tradecredentialregistry.com/exam-covers/310t-truck-and-coach-technician-384.png)310T Truck and Coach Technician](https://tradecredentialregistry.com/practice-exams/310t-truck-and-coach-technician/)
- [![](https://tradecredentialregistry.com/exam-covers/332a-hairstylist-384.png)332A Hairstylist](https://tradecredentialregistry.com/practice-exams/332a-hairstylist/)
- [![](https://tradecredentialregistry.com/exam-covers/442a-industrial-electrician-384.png)442A Industrial Electrician](https://tradecredentialregistry.com/practice-exams/442a-industrial-electrician/)
- [![](https://tradecredentialregistry.com/exam-covers/308a-sheet-metal-worker-384.png)308A Sheet Metal Worker](https://tradecredentialregistry.com/practice-exams/308a-sheet-metal-worker/)
- [![](https://tradecredentialregistry.com/exam-covers/415a-cook-384.png)415A Cook](https://tradecredentialregistry.com/practice-exams/415a-cook/)
- [![](https://tradecredentialregistry.com/exam-covers/456a-welder-384.png)456A Welder](https://tradecredentialregistry.com/practice-exams/456a-welder/)
- [![](https://tradecredentialregistry.com/exam-covers/429a-general-machinist-384.png)429A General Machinist](https://tradecredentialregistry.com/practice-exams/429a-general-machinist/)
- [![](https://tradecredentialregistry.com/exam-covers/339a-hoisting-engineer-mobile-crane-operator-1-384.png)339A Mobile Crane Operator](https://tradecredentialregistry.com/practice-exams/339a-hoisting-engineer-mobile-crane-operator-1/)
- [![](https://tradecredentialregistry.com/exam-covers/339b-hoisting-engineer-tower-crane-operator-384.png)339B Tower Crane Operator](https://tradecredentialregistry.com/practice-exams/339b-hoisting-engineer-tower-crane-operator/)

![Gas Technician 2 (G.2) Practice Exam cover](https://tradecredentialregistry.com/exam-covers/g2-gas-technician-384.png)**$67.49**150 questions

Get the PDF

---

Source: https://tradecredentialregistry.com/practice-exams/g2-gas-technician/